Discription


Operating room (o.r) is an important technical department of a hospital, which provides a place for operation and rescue of patients. Efficient and safe air purification system in operating room ensures sterile environment in operating room. It can meet the high sterile environment for organ transplantation, heart, blood vessel, artificial joint replacement and other operations.

From class 100 to 100,000 and sizes ranges from several square meters to hundreds of square meters, Huakang modular clean room can be customized according to clients' requirements. We are always doing our best to make our products intelligent and operation-friendly with comprehensive solutions.

 

Class

Maximum particles/m3 a

FED STD 209E

≥0.1 μm

≥0.2 μm

≥0.3 μm

≥0.5 μm

≥1 μm

≥5 μm

equivalent

ISO 1

10b

d

d

d

d

e

 

ISO 2

100

24b

10b

d

d

e

 

ISO 3

1,000

237

102

35b

d

e

Class 1

ISO 4

10,000

2,370

1,020

352

83b

e

Class 10

ISO 5

100,000

23,700

10,200

3,520

832

d,e,f

Class 100

ISO 6

1,000,000

237,000

102,000

35,200

8,320

293

Class 1,000

ISO 7

c

c

c

352,000

83,200

2,930

Class 10,000

ISO 8

c

c

c

3,520,000

832,000

29,300

Class 100,000

ISO 9

c

c

c

35,200,000

8,320,000

293,000

Room air

 

Specifications


Related Products